Automatic 1000KVA AC Genset Load Bank Load Bank Cabinet Grey Casing
Color
Product description
1.our load bank an accurately test output power and load capacity
with all kinds of generators.
2.System consists of testing/control and load bank, mainly includes
AC load bank, data capture system, auto load/unload control system,
heat dissipation device, assist control and PC software.
3.User can control load bank through local control panel, also
through software
Technical Parameter
Rating Voltage/Frequency | 400VAC/50Hz, 3 phase 4 wire, |
Voltage range | 400v 50hz ±10% |
Max Rated power | Apparent Power: 1000kVA |
Load Resolution | Resistive load:1.2.2.5.10.10.20.50.100.200.200.200kw |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | AC380VAC/50Hz,3 phase 4 wire |
Wire Connection | Load power supply input——Copper bar (star coupling) |
Communication Interface | RS485, |
Casing Dimensions and Cooling | about 4000*2350*2591mm (length*width*height) Forced air cooling,Horizontal inlet air,Vertical cooling |
Weight | About 3600kgs/set |
Transportation | Hoisting, there are lifting lug in top of casing |
Casing Color | Grey(RAL7035) |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤1500 meter |
Atmospheric Pressure | 86~106kPa |
Contactor | Schneider |
Fuse | DELIXI |
MCU | INFINEON |
Data processing software | Kaixiang(self-developed) |
Alloy Resistance | Kaixiang(self-developed) |
Product Advantage
Real-time parameter: Current, voltage, power, power factor,
frequency, time, etc could be displayed by software.
Safety monitoring: User can know the working conditions of load
bank through software indicating light. When in abnormal stop
protection, software will indicate the reasons of stopping.
Data collection interval: the min saving interval is 2 seconds.
Data saving and in query: testing data could be saved in software,
user can query at any time.
Application
Manufacturers of standby power generators commonly use load banks
to test and tune newly assembled units. When the generator has been
set up in a test cell within the factory, a test engineer uses the
load bank to apply a discrete, selectable electrical load to the
generator and measure the response stability and endurance. During
this process, the test engineer calibrates and adjusts the
generator performance to ensure it meets the intended product
specifications and tolerances.
Hebei Kaixiang Electrical Technology Co., Ltd
Kaixiang intelligent power detection technology is the Chinese industry leader dedicated to providing load testing and maintenance of all types of power, to avoid accidents and economic losses due to power failure. As a national high-tech enterprises, science and technology to create the industry's first Kaixiang municipal enterprise technology center, with the establishment of China's oldest and largest intelligent power detection equipment R & D center and production base, creating the first brand of Chinese power detection "KAIXIANG Load. "
Kaixiang Technology was established in 1994, long-term focus on smart power detection technology development and application in shipbuilding, petroleum, offshore platforms, data centers, communications, power, military, aviation, research institutes and other areas, and in strict accordance with the ISO9001 international quality standard management system for the design, manufacture and service. The company's core technologies are independent research, has seven patents, 10 software copyrights, two corporate standards.Among them, Kaixiang "smart power marine generators AC load," Science and Technology Department of Hebei Province has been named the international advanced level scientific and technological achievements, the enterprise standard "dry AC load" to upgrade the industry standard by the Ministry of publicity.
Kaixiang Technology specializes in generators Intelligent Test System, HV / MV dry load, intermediate load military, RLC load, RCD nonlinear loads, renewable energy detection, smart grid - the development of micro-Grid testing and manufacturing equipment . Products have been widely used in the Jiangnan Shipyard, Huangpu Shipyard, Hudong Shipyard, CNOOC, Shengli Oilfield, CICC, Taikang Life, China Mobile, CNR, Beijing Electric Power, Beijing Institute of Technology, and other famous enterprises, institutions, but also exports to the United Kingdom, Japan, Korea, Australia, Singapore, Thailand and other overseas markets. Currently, there are over 20,000 units KaiXiang load in a well-functioning home and abroad.
KaiXiang load can be applied in shipbuilding, petroleum, offshore platforms, data centers, communications networks, financial, military, weapons, mobile power station, power plant security, mass transit, aviation, aerospace, renewable energy, smart grid - micro-grid, the instrument switches , research and teaching as well as electric vehicle charging management and other fields. Can provide users with the design, manufacture, installation, commissioning, training, maintenance of full service, as well as OEM, leasing and on-site testing services.
Kaixiang Technology at Keppel Shipyard in 2006 developed a sense of one-2926kVA resistance load is the first high-power marine dry AC load;
2009 was developed by the Huangpu Shipyard AC690V-14700K generators Intelligent Test System was the country's largest marine generator set capacity testing equipment;
2009 Zhejiang company developed high-power high-voltage AC load AC10.5kV-1760kW is China's first direct test of high-power high-voltage generators dry load;
Jiangnan Shipyard in 2010 developed AC390-12088K generators Intelligent Test System is a dry load on marine naval initial application.
Kaixiang technology to "quality-oriented, customer first" purpose, "professionalism, objectivity, innovation, efficiency" as a concept. Through our efforts, aimed at creating more value for users. We sincerely hope to cooperate with all walks of life friends, co-guardian of electrical safety, to make life better!